In this page the geometrical and material data for overhead line conductors are specified.
Data |
Description |
Phase no. |
Phase number. 0=ground wire on zero potential (eliminated). For lightning studies sky-wires should be treated as separate phase conductors. |
RESIS |
Conductor resistance at DC (with skin effect) or at Freq. Init. (no skin effect) |
REACT |
The frequency independent reactance for one unit spacing (meter/foot). Only available with no skin effect. |
Rout |
Outer radius (cm or inch) of one conductor |
Rin |
Inner radius of one conductor. Only available with skin effect. |
Horiz |
Horizontal distance (m or foot) from the center of bundle to a user selectable reference line. |
VTower |
Vertical bundle height at tower (m or foot). |
VMid |
Vertical bundle height at mid-span (m or foot). The height h= 2/3* VMid + 1/#*VTower is used in the calculations. |
If Auto bundling checked: |
|
Separ |
Distance between conductors in a bundle (cm or inch) |
Alpha |
Angular position of one of the conductors in a bundle, measured counter-clockwise from the horizontal line. |
NB |
Number of conductors in a bundle. |